Digital I/O modules

Versatile modules for digital signals in hazardous areas
The digital I/O modules (DIOM) are suitable for connecting up to 16 intrinsically safe digital signals. The channels can be used in pairs as inputs for contacts or proximity switches, or as outputs for low-power solenoid valves or indicator lamps. In addition, frequency/counter inputs are available with or without rotation direction recognition.

The digital I/O modules (DIOM) can be used to connect up to 16 intrinsically safe digital signals. All channels can be used in pairs as inputs for passive contacts or NAMUR proximity switches (EN 60947-5-6) or as outputs for low-power solenoid valves or Ex i indicator lamps.

Up to eight inputs can be used as frequency inputs/counters up to 20 kHz, and up to four inputs can be used in the "Rotation direction recognition" and "Forwards/backwards counter" operating modes. The Ex i inputs/outputs are short-circuit proof and galvanically separated from the system.

A blue LED and diagnostic messages provide early warnings that maintenance is required in order to avoid system downtime.
The Zone 1 versions have additional LEDs for each channel to indicate any line faults and the switching state.

  • *Versatile: Channels can be used in pairs as inputs or outputs
  • Versions with Ex ia inputs/outputs for installation in Zone 1 or Zone 2
  • Hot-swappable: Can be replaced while the system is in operation

Filter product lines

Select the product lines that are applicable to your intended use.

Filter product lines

hide
Certificates SAP
Zone Filter
Installation
Class1 Division and Zone
Application range (zones)
Ex interface zone
Max. Voltage Uo
Max. Current Io
Max. power Po
Channel status LEDs

5 Series (6 Products)